e2xb05-e2s-vietnam-den-xenon-vat-lieu-nhua-xenon-strobe-5-joule.png
Ul Iecex-approval Atex-approval Culs-approval Ce-approval
1-31-010

E2xB05 Xenon Strobe 5 Joule

The hazardous area E2xB05 Xenon strobe beacon is UL/cULs approved for Class I Div 2, Class II Div 2, Class I Zone 2/22 as well as IECEx and ATEX certified for Zone 2 and 22 applications.

The E2xB05 is a 5 Joule Xenon strobe beacon with a 1Hz (60 fpm) flash rate. 
The E2x range features enclosures manufactured from lightweight, high performance PPS which, with its corrosion proof properties, is suitable for the harshest of environments.

Specification

 
Energy: 5 Joules (5Ws)
Flash rate: 1Hz (60 fpm)
Peak Candela: 500,000 cd - calculated from energy (J)
Effective Intensity cd: 250 cd - calculated from energy (J)
Peak Candela: 34,122 cd* - measured ref. to I.E.S.
Effective Intensity cd: 108 cd* - measured ref. to I.E.S.
Lens colours: Amber, Blue, Clear, Green,
Magenta, Red & Yellow
Voltages DC: 12Vdc; 24Vdc; 48Vdc
Voltages AC: 115Vac; 230Vac
Ingress protection: IP rating per EN60079-0:IP64
IP rating per EN60529:IP66
Type rating per UL50E/NEMA250:4/4X/13
Enclosure material: UL94V0 PPS & ABS
Lens material: Borosilicate glass dome with PC prismatic lens cover.
Guard: Stainless Steel dome guard as standard
Cable entries: Dual M20x1.5 or 1/2"NPT
Terminals: 0.5 - 2.5mm² (20-14 AWG)
Line monitoring: Blocking diode included
EOL can be factory fitted
Operating temp: -20 to +55°C [-4° to +131°F]
Storage temp: -40 to +70°C [-40° to +158°F]
Relative humidity: 90% at 20°C [68°F]
Weight: 1.48kg/3.25Ibs
* All candela data is representative of performance with clear lens at optimum voltage.

Current Consumption

Version: Voltage: Current:
12V dc   10-14V dc 520mA
24V dc   20-28V dc 275mA
48V dc   42-58V dc 145mA
115V ac 50/60Hz +/-10% 80mA
230V ac 50/60Hz +/-10% 30mA

Part Codes

Part Code: Ident.: Description:
Product type: E2xB05 Xenon Strobe Beacon
Voltage: AC115
AC230
DC012
DC024
DC048
115V ac 50/60Hz
230V ac 50/60Hz
12V dc (10-14V dc)
24V dc (20-28Vdc)
48V dc (42-54V dc)
Cable entries: [e] A
B
C
M20x1.5 & ½” NPT
M20x1.5 & M20x1.5
½” NPT & ½” NPT
Stopping plug material: [m] N Nylon
Bracket & Guard: [s] 1
2
304 (A2) Stainless Steel
316 (A4) Stainless Steel
Version: [v] A1 UL, cULs, IECEx & ATEX
Enclosure: [x] B Black
Lens colour: [y] A, B, C
G, M, R
Y
Amber, Blue, Clear
Green, Magenta, Red
Yellow
e.g: E2xB05DC024BN1A1B/R E2xB05 Xenon Beacon in 24Vdc with dual M20 entries,
nylon stopping plug, UL, cULs, IECEx & ATEX approved
Black enclosure with Red lens
Also available as the E2xC1X05 combined alarm sounder and Xenon beacon and the
E2xC1LD2 combined alarm sounder and LED beacon.

Coding

  • ATEX / IECEx certification
    II 3G Ex nA IIC T3 Gc Ta -20°C to +40°C
    II 3G Ex nA IIC T2 Gc Ta -20°C to +55°C
    II 3D Ex tc IIIC 85°C Dc Ta -20°C to +40°C
    II 3D Ex tc IIIC 100°C Dc Ta -20°C to +55°C
  • NEC Class / Zone ratings US
    Class I Zone 2 AEx nA IIC T3 Gc Ta -20°C to +40°C
    Class I Zone 2 AEx nA IIC T2 Gc Ta -20°C to +55°C
    Zone 22 AEx tc IIIC 85°C Dc Ta -20°C to +40°C
    Zone 22 AEx tc IIIC 100°C Dc Ta -20°C to +55°C
  • CEC Class / Zone ratings Canada
    Class I Zone 2 Ex nA IIC T3 Gc Ta -20°C to +40°C
    Class I Zone 2 Ex nA IIC T2 Gc Ta -20°C to +55°C Zone 22 Ex tc IIIC 85°C Dc Ta -20°C to +40°C
    Zone 22 Ex tc IIIC 100°C Dc Ta -20°C to +55°C
  • NEC & CEC Class / Division Ratings for US / Canada
    Class I, Div 2, ABCD T2D Ta -20°C to +55°C
    Class I, Div 2, ABCD T3 Ta -20°C to +55°C
    Class II, Div 2, FG T5 Ta -20°C to +55°C
    Class II, Div 2, FG T6 Ta -20°C to +40°C
    Class III, Div 1&2 Ta -20°C to +55°C