Alarm Horn: |
|
Maximum output: |
Class I version: 115dB(A) @ 1 metre [106dB(A) @ 10ft/3m]
Class II version: 96dB(A) @ 1 metre [87dB(A) @ 10ft/3m] |
Nominal output: |
Class I version: 110dB(A) @ 1m +/- 3dB – Tone 4 [101dB(A) @ 10ft/3m]
Class II version: 91dB(A) @ 1 metre [82dB(A) @ 10ft/3m] |
No. of tones: |
64 (UKOOA / PFEER compliant) |
No. of stages: |
4 |
Volume control: |
Adjustable -12dB(A) |
Effective range: |
125m/410ft @ 1KHz |
Supply Voltages: |
24Vdc; 115Vac; 230Vac |
Stage switching: |
DC units: negative or positive
AC units: common supply line |
Strobe Beacon: |
|
Energy: |
5 Joules (5Ws) |
Flash rates: |
Option 1: 1Hz (60 fpm)
Option 2: 1.5Hz (90 fpm)
Option 3: Double Strike |
Peak Candela: |
500,000 cd – calculated from energy (J) |
Effective Intensity: |
250 cd – calculated from energy (J) |
Peak Candela: |
46,976 cd* – measured ref. to I.E.S. |
Effective Intensity: |
143 cd* – measured ref. to I.E.S. |
Lens colours: |
Amber, Blue, Clear, Green, Magenta, Red & Yellow |
Tube life : |
Emissions reduced to 70% > 5 million flashes |
General: |
|
Ingress protection: |
EN60529: IP66
UL50E / NEMA250: 4 / 4X / 3R / 13 |
Enclosure material: |
Marine grade aluminium LM6- copper free
Chromated & powder coated – corrosion proof |
Colour: |
Red (RAL3000), Grey (RAL7038) |
Cable entries: |
1 × 1/2"NPT & 2 x M20 x 1.5mm
1 × 1/2"NPT & 2 × 1/2"NPT
1 × 1/2"NPT & 2 × 3/4"NPT |
Terminals: |
0.5 – 2.5mm² (20-14 AWG) |
Grounding stud: |
M5 |
Operating temp: |
24Vdc & 115Vac: -40° to +70°C [-40° to +158°F]
230Vac: -40° to +55°C [-40° to +131°F] |
Storage temp: |
-50° to +70°C [-58° to +158°F] |
Relative humidity: |
95% – Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist |
Weight: |
4.9kg/10.9lbs |