stexcp8-bg-e2s-viet-nam-nut-nhan-vo-kinh-voi-lift-flap-ss316l-model-stexcp8-bg-break-glass.png
Ex-eac-logo Eac-logo Iecex-approval Atex-approval Ce-approval
1-27-120

STExCP8-BG Break Glass

The STExCP8-BG break glass manual call point, featuring 316L stainless steel enclosures, is designed for the harshest of environments. Approved for Zone 1 and 2 hazardous areas for fire and gas alarm systems plus emergency shutdown and process control applications.

Available with standard DIN rail terminals or the innovative E2S termination board providing dedicated connections for field installed EOL and/or series devices. The safety glass element protects the operator and removes the requirement for a hammer to activate the unit. SIL 2 certified to IEC 61508 (2010).

Specification

 
Version: STExCP8-BG
Coding: Ex db IIC T6 Gb Ta. -55°C to +70°C (Single switch)
Ex db IIC T5 Gb Ta. -55°C to +70°C (Dual switch)
Ex db IIC T6 Gb Ta. -55°C to +60°C (Dual switch)
Ingress protection: EN/IEC 60529 - IP66
Housing material: 316L Stainless Steel
Colour: RAL3000 Red (others available on request)
Cable entries: 2 x M20x1.5 top and
1 x M20x1.5 side.
Back box can be rotated to give
2 x bottom and 1 x side entries
Stopping plugs: 2 x 316 Stainless Steel plugs as standard
Brass and Nickel plated plugs optional
Terminals: DIN rail 8 x 2.5mm² SAK2.5 
or
Termination board featuring 6 x 2.5mm² terminals plus 4 x dedicated EOL & Series terminals
Earth: External M5 earth connection
Test: Test key facility
Weight: 4.2Kg/9.26Ibs
 
Voltage Range: Max input Current: Limitations for EOL / Series Resistors:
250Vac Max 5.0A max not permitted
48Vdc Max 1.0A max min. 2.2kOhm
24Vdc Max 3.0A max min. 470 Ohm
 
EOL and Series Diode Values:
xxx: Description Max. current supply permitted
3V3 3.3V Zener Diode 230mA
4V7 4.7V Zener Diode 162mA
5V1 5.1V Zener Diode 149mA
5V6 5.6V Zener Diode 136mA
6V2 6.2V Zener Diode 122mA
6V8 6.8V Zener Diode 112mA
10V 10V Zener Diode 76mA
12V 12V Zener Diode 63mA

Part Codes

Version: Part code:
 
Product type: STExCP8BG Break Glass Manual Call Point
Switch Type: [s] S
D
SPCO/SPDT
DPCO/DPDT
Cable Entry Type:[e]









Note:
A
B
C
D
E
F
G
H
I
J
3 x M20x1.5mm
2 x 1/2" NPT - adaptors
2 x 3/4" NPT - adaptors
2 x M25x1.5mm - adaptors
1 x 1/2" NPT - adaptor
1 x 3/4" NPT - adaptor
1 x M25x1.5mm - adaptor
3 x 1/2" NPT - adaptors
3 x 3/4" NPT - adaptors
3 x M25x1.5mm - adaptors
Unused entries supplied with M20 stopping plugs
Stopping plug
material: [m]
S Stainless Steel [Default]
Terminals: [t] D
P
DIN Rail 8 x SAK2.5
Termination board: 6 x 2.5mm² terminals plus 4 x EOL & Series terminals
Lift flap: [l] L
N
St/St Lift flap
No lift flap
Duty label [d]: 1
2
3
4
5
6
No Duty label, no Equip. tag
Duty label St/St
Duty label St/St + Equip. tag
Duty label Metalised Polyester
Duty label M. Poly. + Equip. tag
Equip. tag only
Product version: [v] A1 IECEx & ATEX & CUTR Ex EAC
Enclosure colour: [x] R, B, N, Y, V, S, K Red, Blue, Green, Yellow
Red/White, Yellow/Black, Black
E.O.L.Module:
[Exxx]
optional
ExxxR
ED1
ExxxZ
Resistor value in Ohms e.g. E470R = 470 Ohm
Diode IN4007 = ED1
Zener diode e.g. E5V1Z = 5.1V
Series Module:
[Sxxx]
optional
SxxxR
SD1
SxxxZ
Resistor value in Ohms e.g. S1K5R = 1.5K Ohm
Diode IN4007 = SD1
Zener diode e.g. S5V1Z = 5.1V
Example: STExCP8BGSASDL1A1R
STExCP8-BG with single switch, 3xM20 entries, stainless steel plugs, DIN rail terminals, lift flap, no duty label or tag, IECEx & ATEX & CTRU approved, red enclosure

Coding

  • Ex db IIC T6 Gb Ta. -55°C to +70°C (Single switch)
  • Ex db IIC T5 Gb Ta. -55°C to +70°C (Dual switch)
  • Ex db IIC T6 Gb Ta. -55°C to +60°C (Dual switch)